ASHRAE® Long Island

American Society of Heating, Refrigerating and Air Conditioning Engineers
ASHRAE Long Island Chapter #6

C T T C

Case Against Balancing Valves
          Balance valves that make it possible to adjust constant flow systems are often used in variable flow systems, but they waste a great deal of energy. This article describes this energy loss and the calculations for determining the energy con-sumption of a constant speed chilled-water system and for a similar variable speed system with no balance valves.
          Thousands of systems installed today prove that variable volume, variable speed chilled-water systems do not require balance valves. Balance valves in variable volume and variable flow chilled-water systems not only waste energy but make these systems difficult, if not impossible, to control. A previous ASHRAE Journal article1 shows that no reason exists to install balance valves on a variable flow system.

Constant and Variable Flow Systems
          Figure 1 is a typical piping sche-matic for a constant speed, constant flow chilled-water system incorporating bal-ance valves and three-way control valves on all terminal loads such as coils and other heat exchangers. Figure 2 describes a typical variable volume chilled-water system with a bypass valve to regulate minimum flow in the chiller evaporator. The piping installation shown in Figure 2 costs less than that shown in Figure 1.

Energy Loss and Balance Valves
          The added piping cost is minimal compared to the cost of energy for the constant flow system shown in Figure 1. The total energy cost of balance valves extends beyond the costs associated with losses through the valves themselves. Fig-ure 3 provides the pump flow and head required for a variable flow system and a similar constant flow system. This ex-ample is for an actual 180 ton (633 kW) chilled-water system with a temperature differential of 12°F (7°C) or 2 gpm/ton (0.036 L/(s · kW) for a flow of 360 gpm (23 L/s). Assume that a 200 ton (703 kW) chiller was selected with a flow of 2 gpm/ton (0.036 L/(s · kW) or 400 gpm (25 L/s). Figure 4 provides similar head and flow data with a 225 ton (791 kW) chiller selected instead. The system then was designed for 225 ton (791 kW) at a flow of 450 gpm (28 L/s) and a total dynamic head of 90 ft (269 kPa) when the 225 ton (791 kW) chiller was selected.    

          (DSF) of around 11% for the 200 ton (703 kW) chiller and 25% for the 225 ton (791 kW) chiller. Evaluation of many exist-ing systems have indicated DSFs as high as 50%, resulting in flows and pump heads much higher than the actual opera-tional flow and head. A study of a hotel in California2 showed that a 350 ton (1231 kW) chilled-water system was in-stalled on a 250 ton (879 kW) load for a DSF of 40%. Added capacity is needed for reasons of redundancy and future growth.
          One of the great advantages of a properly designed, variable flow chilled-water system is that the system operates at the actual load on the system, regardless of DSF or allowances for future expansion. In this case, as indicated previously, the actual design flow for the variable flow system is 360 gpm (23 L/s) compared to 400 gpm (25 L/s) for the constant volume system with a DSF of 11% and a second system with a DSF of 25% and a flow of 450 gpm (28 L/s). The overall DSF is a summation of all other safety factors such as diversity, load, and friction.

Constant Flow and Variable Flow Systems Operation
          Most existing constant flow systems use three-way coil con-trol valves as shown in Figure 1. This is the system that is used in this evaluation of constant flow systems.
          Figures 3 and 4 show a pump flow-head curve, a system head curve for a variable flow system, and a point of operation for a constant flow system. The design points are shown as 400 gpm (25 L/s) at 70 ft (209 kPa) head and 450 gpm (28 L/s) at 90 ft (269 kPa), respectively. The point of operation for all three systems is 360 gpm (23 L/s) because that is the actual maxi-mum flow required for each. The difference between the point of operation and the design flow is the flow reduction achieved through the use of balance valves on the constant flow systems.
          Compare these points of operation for the constant flow system to the path of operation of a properly designed vari-able flow, variable speed system. In this case, the setpoint required at the controlling differential pressure transmitter is 10 ft (30 kPa). This is the head required for the branch with the highest pressure drop. 
          The path of operation is on the uniform system head curve for the variable flow system. The system will never reach the design points for the constant flow systems because no requirement exists in the system for these high flows and heads.

Energy Waste of Balance Valves
          The energy waste of balance valves is due to their use being based upon constant flow in a system that has a variable load. The system operates at 360 gpm (23 L/s), regardless of the cool-ing load using much more energy than the vari-able flow system shown in Figures 3 and 4. The following energy calculations are based upon a chilled-water system that operates from March to October for an annual operation of 5,880 hours.
          The same equation for brake horsepower is used for constant and variable speed pumps. The basic equation is:
    
          The data in this article assumes that the chiller plant is cooled by this chilled water. If not, then the efficiency of the mo-tors and variable speed drives must be deducted from the calculations.
          The calculation of the energy consumption for the constant flow systems is simple since the pump always operates at one point, 360 gpm (23 L/s) at 73.5 ft (220 kPa) head for the system with an 11% DSF and 360 gpm (23 L/s) at 100 ft (299 kPa) head for the system with a 25% DSF. The annual energy consumption for the constant flow system with an 11% DSF is 40,219 kWh and 57,211 kWh for the system with a 25% DSF. These values were determined using high efficiency motors with 0.8 kW (1.07 kW/kW) per brake horsepower or 92% efficiency.
   
          The calculations for the energy consumption of the variable flow system are much more complex since they must be made at 10 points on the system head curve along with the extra energy that is consumed by minimum flow through the chiller.
          Tables 1 and 2 describe these calculations with data secured from the pump flow-head curves of Figures 3 and 4. The wire-to-shaft efficiencies and percent of load in Columns E and G are from the authors’ experience with variable primary pumping systems. The pump energy for maintaining minimum flow in the chillers for the values up to 108 gpm (7 L/s) must be added to the total kW in Tables 1 and 2. This energy consumption is not great since the flow and head are at minimums. The calculation for this energy reveals that the energy to be added is 264 kWh for the 11% DSF system and 325 kWh for the 25% DSF system.
          The energy totals are 12,142 kWh for the variable flow system with the 11% DSF and 13,528 kWh for the system with a 25% DSF. If you subtract these totals from those for the constant flow systems, you get 27,813 kWh saving or 68% for the 11% DSF system and 43,358 kWh or 76% for the 25% DSF system. A summary of actual annual measurement and verification on a large 24/7 hotel facility in California is available in Reference 2. Interestingly, the net pump energy sav-ings by eliminating bal-ance valves and incorporating variable speed pumps was 80%.
          The earlier figures are for pumping energy alone and do not include the thermal equivalent of the pumping. An estimate for this energy is achieved by multiplying the energy lost in kWh by 3,413 Btu (3600 kJ), the heat content of a kWh and dividing by 12,000 Btu (12 660 kJ), the heat content of a ton of cooling. If the overall production of a ton of cooling re-quires 0.9 kW/ton (0.256 kW/kW) in the chiller plant, the added savings for the 11% DSF system would be 7,119 kWh for a total of 37,408 kWh and 11,099 kWh for a total of 54,457 kWh for the 25% DSF system.
          These totals are almost unbelievable, since a combination of energy saved in pumping and in the chiller plant is almost equal to the total energy of the pumping for the constant flow system. Since these savings are for a 180 ton (633 kW) system operating 5,880 hours per year, if you divide the savings by these two figures, you achieve a kW/ton figure of 0.035 and 0.052 (0.01 kW/kW and 0.015 kW/kW), respectively. This provides us with a simple number that can be used to estimate quickly whether a system should be evaluated for replacing three-way valves and constant speed pumps with a variable volume system.
          If we round off these numbers to 0.04, we can proceed to make a quick estimate for a larger system. For example, a 5,000 ton (17 585 kW) system operating 7,000 hours/year, the rough savings is 1.4 million kWh per year. If the electrical rate is $0.12/kWh, this amounts to $168,000 per year. This is a hypothetical case, but the procedures used here can be used to evaluate any existing chilled-water system.
          Assume that 20,000 chiller plants were in the U.S. at the end of 2008 and that these plants had a capacity of 16 mil-lion tons (5 627 200 kW). If we also assume that half of these plants are still constant flow with three-way coil valves and balance valves operating around 5,000 hours per year, with an overall savings factor of 0.04 kWh per ton/hour, the sav-ings in electric generat-ing plant capacity would be 320 MW and 1.6 million MWh in energy consumption. These are just gross estimates. However, are they not huge enough to encourage us to (1) stop designing variable flow systems with balance valves and constant speed pumps and (2) search for existing chilled-water systems to find those that are candi-dates for conversion to variable flow systems without balance valves?


Conclusions
          Design chilled-water systems with variable speed pumps, high performance two-way coil control valves, and no balance valves. The coil control valves must have a high shut-off pres-sure, a broad turn-down range, and at least a Level V bub-ble test in accordance with ANSI Standard 70-2-2003, Control Valve Seat Leakage.
          If you have a chilled-water system with three-way coil valves and balance valves, consider converting it to a true variable vol-ume system. Do a quick check by securing the annual number of hours of operation and the actual tons of cooling for your system. Multiply these two figures by 0.04 kW/ton (0.14 kW/kW) to get an estimated annual savings in kWh for con-verting to variable flow and opening the balance valves wide. Multiply your annual savings in kWh by your composite electrical rate to get a rough estimate of your annual monetary savings. This number will help you decide whether you should do an intensive study of your system for conversion to variable flow.
  
Brian Simkins
CTTC
bbbbCTTC
Article In:
ASHRAE Journal, July 2009. Please see article for all references and credits.
By Gil Avery, P.E., Fellow/Life Member ASHRAE; and James B. (Burt) Rishel, P.E., Fellow/Life Member ASHRAE